XN2-1 Mains Decoupling Relay

Previous
Next

XN2-1 Mains Decoupling Relay

Category Grid decoupling
1,370.00 CHF
On backorder

The relay XN2 of the easy PROFESSIONAL LINE is a universal mains decoupling relay and contains the protective functions required for the mains parallel operation of power stations:

  • Over- and undervoltage protection
  • Over- and underfrequency protection
  • Phase sequence supervision
  • in addition, for the XN2-1: vector surge (fast decoupling of the generator in case of mains failure)

Characteristics

ANSI Schutz 27/59 78V 810/81U

Protection Settings

Parameter       Setting Range

V<         75% … 100% × V n (cont.)

V>         100% … 125% × V n (cont.)

f<           97.5% … 100% × f n (cont.)

f>           100% … 102.5% × f n (cont.)

Vector surge tripping ΔΘ or df/dt supervision         1 … 22° el. or 0.5 … 3 Hz/s

tv           5 s (fixed)

Switching hysteresis for V<, V>        3%, 10%

Switching hysteresis for f<, f>           0.25% (fixed)

Blocking voltage VB<              20% … 70% × V n (cont.)

Auxiliary Voltage

Voltage supply via wide-range power supply unit:.